NYY-J 5-Core 25mm², Black AC cable 0.6/1kV . Batts
NYY-J 5 Core 25mm², high tuff. Price per meter. Quantity determines the number of meters.
NYY-J 5-Core 25mm², Black AC cable, Single Phase, 0.6/1kV - Batts
This VDE approved cable is made in Germany with high quality double PVC insulation. NYY-J cables are versatile and durable, they can be installed outdoors, underground, in brick and concrete walls. This type of cable has exceptional resistance to UV radiation and all waether conditions. The operating temperature is -40°C to +70°C.
Applications and Usage
It is used an power and control cable. The ideal use is in single phase power supplies and solar systems. It can be connected as the main AC output cable to all our solar inverters.
Outdoors, underground, in brickworks. It is compliant with UK wiring regulation such as BS7671 for installation (burial) in the ground). It is also suitable for installation in conduit for extra protection against mechanical stress.
The High-Tuff , NYY cable is suitable for outdoor use (UV resistant)
NYY-J is a VDE approved, solid conductor*, black PVC jacketed, 600/1000 volt power and control cable.
- Conductor: Class 1 solid plain copper to
BS EN 60228:2005 (previously BS6360), VDE0295, IEC 60228, CENELEC HD383 - Insulation
PVC (Polyvinyl Chloride) Type YI4 to VDE0276 - Sheath
FR/PVC (Flame Retardant / Polyvinyl Chloride) Type YM3 to VDE0276 - Sheath Colour
Black
- Voltage Rating
600/1000V - Temperature Rating
Fixed: -40°C to +70°C
Flexing: -5°C to +50°C - Minimum Bending Radius
Single Core: 15 x overall diameter
Multi-Core: 12 x overall diameter - Core Identification
Up to and including 5 cores:
colour coded
Download Data Sheet from Helukabel
NYY power cable to IEC60502
Conductors: Plain annealed copper conductors
Insulation: PVC (Polyvinyl-Chloride)
Core identification:5 Core (black, blue, brown, grey & green/yellow)
Sheath/Jacket: PVC (Polyvinyl-Chloride)
Colour: Black
Voltage: 600/1000v
Operating temperature: Maximum 70°C, minimum bending 0°C
Types: O - Excluding protective earth conductor. J - Including protective earth conductor
Standard: VDE0271 Power cables. Specifications for power cables 0.6/1kv and above for special applications
DIN VDE 0276-603 Power cables Part 603 distribution cables of rated voltage 0.6/1kv
DIN VDE 0276-627 Power cables Part 627 multicore & multipair cables for installation above and below ground
IEC60502 Power cables with extruded insulation and their accessories for rated voltages from 1kV to 30kV
Applications: Energy cables for use in open air, underground, indoors and in cable ducts
Minimum Bending Radius: 15 x Overall Diameter for Solid Conductors. 12 x Overall Diameter for Stranded Conductors